9/30/99 AC 27-1B
fuel, fumes and potential ignition sources (i.e., “potential hazards”). Each fireproof
protective device must, by regulation, meet the following criteria:
(1) Its design and location must take into account the probable fire path from
each fire zone or source considering factors such as internal airflow, external airflow,
and gravity.
(2) It must be constructed so that no hazardous quantity of air, fumes, fluids, or
flame can propagate through it to unprotected parts of the rotorcraft.
(3) Its openings (e.g., shaftholes, lineholes, etc.) must be sealed with close
fitting fireproof grommets, bushings, bearings, firewall, fittings, or equivalent that prevent
burn through and leakage of hazardous fumes or fluids from the fire zone.
(4) It must be fireproof (see definition).
(5) It must be either corrosion resistant or otherwise safely protected from
corrosion.
b. Definitions.
(1) Fireproof Protective Device. A fireproof protective device is a device such
as a firewall, shroud, enclosure, or equivalent used to isolate a heat or potential fire
source (severe fire) from personnel compartments and from critical aircraft components
which are essential for a controlled landing.
(2) Fireproof. Fireproof is defined in § 1.1 “General Definitions.”
(3) Controlled Landing. A landing which is survivable (i.e., does not fatally
injure all occupants) but may produce an unairworthy, partially salvageable, or
unsalvageable rotorcraft.
(4) Severe Fire. See Definition in paragraph AC 27.859.
c. Procedures. Fireproof protective devices are typically certified by analysis,
tests, or a combination conducted during the certification process, including flight tests
or simulated flight tests, as follows:
(1) Fireproof protective devices should be provided wherever a hazard exists
which requires isolation from a severe fire to avoid fires in personnel compartments and
to avoid thermal damage to critical components (such as structural elements, controls,
rotor mechanisms, and system components) that are necessary for a controlled landing.
A thorough hazard analysis should be conducted during certification to identify, define
and quantify in order of severity (i.e., maximum temperature, hot exposed area, etc.) all
thermal hazards or zones that require fireproof protection in a given design. Engines
(including the combustor, turbine, and tailpipe sections of turbine engines), APU’s,